Reads processed history data of the point.
Namespace: Ico.Fwx.ClientWrapperAssembly: IcoFwxClientWrapper (in IcoFwxClientWrapper.dll) Version: 10.97.212.0 (10.97.212.00)
Syntax
C# |
---|
public IEnumerable<SampleValue> HistoryReadProcessed(
string pointName,
DateTime startTime,
DateTime endTime,
double resampleInterval,
string aggregateTypeName,
AggregateConfiguration aggregateConfiguration,
int readTimeout
) |
Visual Basic |
---|
Public Function HistoryReadProcessed ( _
pointName As String, _
startTime As DateTime, _
endTime As DateTime, _
resampleInterval As Double, _
aggregateTypeName As String, _
aggregateConfiguration As AggregateConfiguration, _
readTimeout As Integer _
) As IEnumerable(Of SampleValue) |
JScript |
---|
public function HistoryReadProcessed(
pointName : String,
startTime : DateTime,
endTime : DateTime,
resampleInterval : double,
aggregateTypeName : String,
aggregateConfiguration : AggregateConfiguration,
readTimeout : int
) : IEnumerable<SampleValue> |
Parameters
- pointName
- Type: System..::..String
Point name to read data from.
- startTime
- Type: System..::..DateTime
Beginning of period to read.
- endTime
- Type: System..::..DateTime
End of period to read.
- resampleInterval
- Type: System..::..Double
Interval between returned aggregate values. 0 indicates that there is no interval defined. The value is in milliseconds.
- aggregateTypeName
- Type: System..::..String
Name of the aggregate to be used when retrieving processed data (use Ico.Fwx.ClientWrapper.AggregateTypeNames).
- aggregateConfiguration
- Type: Ico.Fwx.ClientWrapper..::..AggregateConfiguration
Specifies the processing details.
- readTimeout
- Type: System..::..Int32
Timeout for the read operation. The value is in milliseconds.
Return Value
Collection of the SampleValue items.
See Also